ERV and HRV Ventilation Testing and Balancing in Massachusetts
Massachusetts requires the installed whole-house ventilation system to be tested and verified by a HERS rater, HERS Rating Field Inspector or BPI professional (225 CMR 22 R403.6.3 and the base code). Home Energy Efficiency Consultants measures supply and exhaust airflow, balances the ERV or HRV to the design rate set from your blower door test, and gives you the documentation the inspector needs.
Why balance matters
An unbalanced ERV pushes the house positive or negative. Positive pressure drives moist air into walls in winter; negative pressure pulls in damp, dirty air from crawlspaces, garages and walls.
How the Blower Door Sets Your Ventilation Rate
Massachusetts calculates the minimum continuous rate as 0.03 × floor area + 7.5 × (bedrooms + 1) − 0.052 × Q50 × S × WSF. Q50 is the measured leakage from the blower door test, S is a story factor (1.00, 1.32 or 1.55) and WSF is a county factor (0.66 in Suffolk County).
Example: a 2,000 sq ft, 3-bedroom, 2-story home in Suffolk County that tests at 1,000 cfm50 needs about 45 cfm. Tightened to 425 cfm50, the same house needs about 71 cfm. The tighter the house, the more mechanical ventilation it needs.
More detail: mechanical ventilation CFM requirements.

Why Proper Balancing Is So Important

In a tight house, even a small mismatch between supply and exhaust changes the pressure of the whole home:
- Too much exhaust (negative pressure): the house pulls replacement air through walls, the garage and the basement, which can bring in dust, fumes and soil gases, and can backdraft fuel-burning appliances.
- Too much supply (positive pressure): warm, moist indoor air is pushed into wall and attic cavities in winter, where it can condense and grow mold.
- Wrong total airflow: too little leaves stale, humid air; too much wastes energy and dries the house out in winter.
We measure supply and exhaust with a calibrated flow hood or flow grid, adjust with your HVAC contractor until they match the design rate, and document it for the inspector. See ventilation testing and balancing.
How an ERV Works

- Two fans run continuously: one brings fresh outdoor air in, the other pulls stale air out of kitchens, baths and laundry.
- Both airstreams pass through the core side by side but never mix.
- In winter the warm outgoing air pre-warms the cold incoming air, so you get fresh air without a big heating penalty (code requires 65%+ sensible recovery).
- In summer an ERV also moves some humidity from the incoming air to the outgoing stream. An HRV recovers heat only.
Choosing between them? See ERV vs. HRV.
What We Test
- Supply and exhaust airflow at the ERV/HRV, measured with a flow hood or flow grid (RESNET 380 or ACCA 5).
- Supply and exhaust within balance of each other, so the house is not pressurized or depressurized.
- Delivered airflow compared with the design rate.
- Bath and kitchen exhaust rates.
- Inlet location, dampers and controls checked against R403.6.7.
Common Problems We Find
- ERV left on the factory default speed, far above or below the design rate.
- Supply and exhaust out of balance because of crushed flex duct or unadjusted dampers.
- Outdoor intake too close to a dryer vent or plumbing vent.
- Controls set to intermittent or turned off, so the system is not continuous.
Moisture or condensation already? See moisture and mold in tight new homes.
One Visit With Your Final
We usually test ventilation during the final HERS rating inspection, along with the blower door and duct leakage tests. Need equipment sizing too? See Manual J, S and D.
FAQ
Is ventilation testing required in Massachusetts?
Yes. The installed whole-house ventilation system must be tested and verified (R403.6.3) by a HERS Rater, HERS Rating Field Inspector or BPI Certified Professional.
How does the blower door test affect ventilation?
The measured leakage (Q50) is part of the Massachusetts ventilation formula. A tighter house gets less infiltration credit and needs more mechanical ventilation.
What does balancing an ERV mean?
Adjusting supply and exhaust airflow so they match the design rate and each other, so the house is not pushed positive or negative.
Can you fix an ERV that fails the airflow test?
We find the cause (fan speed, dampers, duct problems), help your HVAC contractor adjust it, and retest.
Do existing homes need ventilation testing?
Code testing applies to new systems in new construction and covered projects. We also test existing homes with moisture or air quality problems.
Town-by-Town Permit Checklists
Local building department details, checked on each town's own website:
Sources: 225 CMR 22 (Stretch/Specialized residential) · 780 CMR 10th edition residential energy amendments. Code text current as of October 2026; DOER has proposed updates to the Stretch and Specialized codes, so confirm before you file.
Related: Stretch code report for permitting · What triggers a HERS rating · REScheck and COMcheck · Phius verification
Schedule Ventilation Testing
Send your plans today. Most projected HERS reports are ready in about one business day after the quote is accepted.
Mass Save®-Listed HERS Rater
Trusted Partner — Verified
Partner
Passive House Verifier
Member★★★★★136 Google
Reviews
The Phius Certified Verifier logo is used under license from Phius.